S(F)Z11-6300~80000/110 Three-phase double-winding on-load tap-changing power transformer
+
  • S(F)Z11-6300~80000/110 Three-phase double-winding on-load tap-changing power transformer

S(F)Z11-6300~80000/110 Three-phase double-winding on-load tap-changing power transformer

The main standards implemented are GB1094, GB/16451, JB/13837, and GB24190.

Quality Assurance

Well made

Worry-free after-sales service

Quality Assurance

Classification:

66kV-220kV Oil-immersed Transformer

Product Introduction

Operating Environment Conditions

1. Altitude ≤2500m

2. Max. ambient temperature; +40℃

3. Max. annual average temperature; +20℃

4. Max. daily average temperature: +30℃

5. Min. outdoor temperature: -30℃

Main Applicable Standards

GB1094、GB/16451、JB/13837、GB24190

Transformer Insulation Level

L|480AC200-L|325AC140/L|175AC35

(LV 10kV Class)

L|480AC200-L|325AC140/L|65AC25

(LV 6kV Class)

Main Technical Parameters

 

Type

Voltage combination
(kV)

 

Connection
symbo

 

No-Load loss
kW

 

Load loss
(75)kW
%

 

No-load
current
%

 

Short-circuit
impedance
(%)

H-V
kV

L-V
kV

S(F)Z11-6300/110

 

 

 

 

110±8×1.25

 

 

 

6.3
6.6
10.5
11

 

 

 

 

YNd11

8.00

34.20

0.72

 

 

 

 

10.5

S(F)Z11-8000/110

9.60

42.75

0.72

S(F)Z11-10000/110

11.36

50.35

0.67

S(F)Z11-12500/110

13.44

59.85

0.67

S(F)Z11-16000/110

16.16

73.15

0.62

S(F)Z11-20000/110

19.20

88.35

0.62

S(F)Z11-25000/110

22.72

104.50

0.58

S(F)Z11-31500/110

27.04

126.35

0.58

S(F)Z11-40000/110

32.32

148.20

0.52

S(F)Z11-50000/110

38.24

184.30

0.52

S(F)Z11-63000/110

45.44

222.30

0.47

S(F)Z11-80000/110

52.00

281.00

0.30

12.0

Note: Table 1 shows the national standard performance parameters. According to customer requirements, our company can provide products with different performance parameters.

According to customer requirements, our company can provide self-cooled products as well as products with other voltage combinations.

Type

TotAL
(kg)

(mm)Out-Line Dimentaion

L

B

H

HL

A1

A2

S(F)Z11-6300/110

25460

5100

4080

4800

6500

2040

1435

S(F)Z11-8000/110

28310

5190

4130

4860

6880

2040

1475

0000/11C

31550

5200

4320

4870

7000

2040

1475

S(F)Z11-12500/110

35340

5575

4380

4910

7300

2040

1475

S(F)Z11-16000/110

39670

5255

4360

5175

7160

2040

1435

S(F)Z11-20000/110

43970

5285

4360

5310

7160

2040

1435

S(F)Z11-25000/110

46290

5410

4500

5330

8080

2040

1475

S(F)Z11-31500/110

55060

5865

4420

5500

8115

2040

1475

S(F)Z11-40000/110

62935

7140

4890

6195

8600

2040

1475

S(F)Z11-50000/110

78140

7345

4310

5330

8000

2040

1475

S(F)Z11-63000/110

81760

7215

5425

6700

8680

2040

1475

S(F)Z11-80000/110

90500

7320

5405

6870

9200

2040

1475

Note: The total weight and overall dimensions of the transformer are for reference only, and the actual dimensions shall prevail as per the outline drawing of the transformer.