10kV dry-type transformer
+
  • 10kV dry-type transformer

10kV dry-type transformer

10kV dry-type transformers are suitable for installation in places with limited space, requiring proximity to the load center, and requiring fire and explosion protection, such as urban centers, residential areas, hospitals, schools, hotels, high-rise buildings, commercial centers, transportation hubs; industrial parks, petrochemical plants, offshore drilling rigs, and other places where oil-immersed transformers are not suitable.

Quality Assurance

Well made

Worry-free after-sales service

Quality Assurance

Classification:

6kV-35kV dry-type transformer

Product Introduction

[xss_clean][xss_clean]

  10kV 级干式变压器适用丁安装在空间有限,需要靠 近负荷中心,要求防火、防爆的场所,如城市中心区、 住宅小区、医院、学校、酒店、高层建筑、商业中心、 交通枢纽;工业园区、石化工厂、海上钻台等不宜采用油 浸式变压器的地方。

  13 型产品较 GB/T10228-2008《 干式电力变压器技 术参数和要求》A 组性能指标,空载损耗下降40%,负载 损耗下降15%,综合费用极低。

  11型产品较GB/T10228-2008《 干式电力变压器技术 参数和要求》A 组性能指标,空载损耗下降 3 0 % , 负 载 损耗下降5%,综合费用低。

变压器进、出线方式

  变压器高低压两侧均可采用上部或下 部进线方式,外壳顶部已预留进线口,对 于下部进线,外壳配有电缆卡,用于固定 进线电缆。

  变压器低压也可以提供标准封闭母 线,标准横排侧出线和标准立排侧出线方 式(需定制)。

10kV 级干式变压器外型图

SCB10-30~2500环氧树脂浇筑干式变压器参数

 

型号
Type



高压
H-V
KV

 

 

 

11
10.5
10
6.3
6

电压组合及分接范围
Vollaye combiralion (kV)
高压分接范围
Tapping  range
H-V



低压
L-V
kV

 

联接组标号
Connectior 

symbol

短路阻抗
Short circuit
impedance
(%)

空载损耗
No.Load loer
kW

负载损耗 

Load
loss
kW

空载电流
No-load
current
(%)

SC10-30

 

 

 

 

 

±5%
±2×2.5%

 

 

 

 

0.38
0.4  

0.415 

0.433

 

 

 

 

 

YynO
Dyn11

 

 

 

4%

0.19

0.71

2.1

SC10-50

0.27

1.00

2.1

SC10-80

0.37

1.38

1.6

SC10-100

0.4

1.57

1.6

SC10-125

0.47

1.85

1.5

SC10-160

0.54

2.13

1.5

SC10-200

0.62

2.53

1.3

SC10-250

0.72

2.76

1.3

SC(B)10-315

0.80

3.47

1.1

SC(B)10-400

0.98

3.99

1.1

SC(B)10-500

1.16

4.88

1.1

SC(B)10-630

 

 

6%

1.3

5.96

0.9

SC(B)10-800

1.52

6.96

0.9

SC(B)10-1000

1.77

8.13

0.9

SC(B)10-1250

2.09

9.69

0.9

SC(B)10-1600

2.45

11.73

0.9

SC(B)10-2000

3.05

14.45

0.9

SC(B)10-2500

3.6

17.17

0.7

SCB11-30~2500环氧树脂浇筑干式变压器参数

 

型号
lype

电压组合及分接范围
Voltage combination (kV)

联接组标
号
Connection
symbol

短路阻抗
Short
circuit
mnedanns
(%)

空载损耗
No-Load
loss
kW

 

负载损耗
Load loss
kW

空载电流 

No-load current
(%)

高压
H-V
kV

高压分接范围
Tapping range
HV

低压
L-V
kV

SC11-30

 

 

 

 

11
10.5
10
6.3
6

 

 

 

 

 

±5%
+2×2.5%

 

 

 

 

0.38
0.4
0.415
0.433

 

 

 

 

 

Yyn0
Dyn11

 

 

 

4%

0.17

0.71

1.9

SC11-50

0.24

1.00

1.9

SC11-80

0.33

1.38

1.5

SC11-100

0.36

1.57

1.5

SC11-125

0.42

1.85

1.3

SC11-160

0.48

2.13

1.3

SC11-200

0.55

2.53

1.1

SC11-250

0.64

2.76

1.1

SC(B)11-315

0.79

3.47

1.0

SC(B)11-400

0.88

3.99

1.0

SC(B)11-500

1.04

4.88

0.9

SC(B)11-630

 

 

6%

1.17

5.96

0.9

SC(B)11-800

1.36

6.96

0.9

SC(B)11-1000

1.59

8.13

0.9

SC(B)11-1250

1.88

9.69

0.9

SC(B)11-1600

2.2

11.73

0.7

SC(B)11-2000

2.74

14.45

0.6

SC(B)11-250C

3.24

17.17

0.6

SCB12-30~2500环氧树脂浇筑干式变压器参数

 

型号
Type

  
高压
H-V
kV

电压组合及分接范围
Voltage combination (kV)

高压分接范围 

Tapping range



低压
L-V
kV

 

联接组标号
Connection symbol

短路阻抗
Short
circuit
impedance
(%)

空载损耗
No-Load 

loSS
kW

负载损耗
Load
055
kW

空载电流
No-load
curreni
(%)

SC12-30

 

 

 

 

11
10.5
10
6.3
6

 

 

 

 

 

+5%
±2x2.5%

 

 

 

 

0.38
0.4
0.415
0.433

 

 

 

 

 

Yyn0
Dyn11

 

 

 

4%

0.15

0.71

2.4

SC12-50

0.215

1.00

2.4

SC12-80

0.295

1.38

1.8

SC12-100

0.32

1.57

1.8

SC12-125

0.375

1.85

1.6

SC12-160

0.43

2.13

1.6

SC12-200

0.495

2.53

1.4

SC12-250

0.575

2.76

1.4

SC(B)12-315

0.705

3.47

1.2

SC(B)12-400

0.785

3.99

1.2

SC(B)12-500

0.93

4.88

1.0

SC(B)12-630

 

 

6%

1.04

5.96

1.0

SC(B)12-800

1.215

6.96

1.0

SC(B)12-1000

1.415

8.13

1.0

SC(B)12-125C

1.67

9.69

1.0

SC(B)12-1600

1.96

11.73

1.0

SC(B)12-2000

2.44

14.45

0.8

SC(B)12-2500

2.88

17.17

0.8

SCB13-30~2500 环氧树脂浇筑干式变压器参数

 

型号
Type

由压组合及分接范围
Voltage combination (kV)

联接组标号
Connection
symbo

短路阻抗
Short  circuit
mpedance
(%)

空载损耗
No-Load

loss
kW

负载损耗 

Load
loss
kW

空载电流
No-load
current 

(%)

高压
H-V
kV

高压分接范围
lapping range
H-V

低压
L-V
kV

SC13-30

 

 

 

 

11
10.5
10
6.3
6

 

 

 

 

 

±5%
±2×2.5%

 

 

 

 

 

0.38
0.4
0.415
0.433

 

 

 

 

 

Yyn0
Dyn11

 

 

 

4%

0.135

0.64

2.4

SC13-50

0.20

0.90

2.4

SC13-80

0.265

1.24

1.8

SC13-100

0.29

1.41

1.8

SC13-125

0.34

1.66

1.6

SC13-160

0.39

1.91

1.6

SC13-200

0.445

2.27

1.4

SC13-250

0.52

2.48

1.4

SC(B)13-315

0.635

3.12

1.2

SC(B)13-400

0.71

3.59

1.2

SC(B)13-500

0.835

4.39

1.0

SC(B)13-630

 

 

6%

0.94

5.36

1.0

SC(B)13-800

1.09

6..26

1.0

SC(B)13-100C

1.27

7.31

1.0

SC(B)13-1250

1.50

8.72

1.0

SC(B)13-1600

1.76

10.50

1.0

SC(B)13-2000

2.19

13.00

0.8

SC(B)13-2500

2.59

15.40

0.8

Tag: