The impact of transformer performance on short-circuit impedance


Time:

2026-08-07

When a transformer operates at full load, the short-circuit impedance significantly affects the output voltage on the secondary side. Lower short-circuit impedance results in a smaller voltage drop, while higher impedance leads to a larger voltage drop. When a short circuit occurs in the transformer load, a lower short-circuit impedance results in a larger short-circuit current, and the transformer experiences a greater electrodynamic force. Conversely, a higher short-circuit impedance results in a smaller short-circuit current, and the transformer experiences a smaller electrodynamic force.

Short-circuit impedance refers to the resistance formed by a short circuit in an electrical appliance, such as eddy currents. The short-circuit impedance of a transformer, at rated frequency and reference temperature, is the equivalent series impedance between the terminals of one winding in a pair of windings, Zk = Rk + jXk. Because its value must be determined through load testing in addition to calculation, it is conventionally also called short-circuit voltage or impedance voltage.

We've all learned physics: a current-carrying conductor in a magnetic field experiences mechanical force. Therefore, when current flows through a transformer winding, the interaction between the current and the leakage magnetic field generates an electromagnetic mechanical force within the winding. The magnitude of this force depends on the magnetic flux density of the leakage field multiplied by the conductor current. We also know that the direction is determined by the left-hand rule. When a transformer is operating under normal load, the force acting on the conductor is relatively small. However, in the event of a sudden short circuit, the maximum short-circuit current will be 25% to 30% of the rated current, or even greater. According to the formula, the electromagnetic force generated between the windings during a short circuit is proportional to the square of the short-circuit current. Therefore, the mechanical force during a short circuit will be hundreds of times greater than the force during normal operation, and this force is generated very quickly. In such a short time, the circuit breaker cannot disconnect the circuit.

The transformer short-circuit impedance, also called impedance voltage, is defined in the transformer industry as follows: when the secondary winding of a transformer is short-circuited (steady-state), the voltage applied to the primary winding while the rated current flows is called the impedance voltage Uz. Uz is usually expressed as a percentage of the rated voltage, i.e., uz = (Uz/U1n) * 100%.

In short, under the influence of a large short-circuit electromagnetic force, many parts in the transformer windings may be damaged. Therefore, when designing transformers, manufacturers must study and verify the transformer's ability to withstand short-circuit electromagnetic forces and the mechanical strength of the windings under short-circuit conditions. To ensure the normal operation and use of the transformer, we must consider the stress on the transformer.

When the transformer is running at full load, the level of the short-circuit impedance has a certain impact on the level of the secondary side output voltage. A smaller short-circuit impedance results in a smaller voltage drop, and a larger short-circuit impedance results in a larger voltage drop. When a short circuit occurs in the transformer load, a smaller short-circuit impedance results in a larger short-circuit current, and the transformer experiences a larger electrodynamic force. A larger short-circuit impedance results in a smaller short-circuit current, and the transformer experiences a smaller electrodynamic force.