How to detect and address transformer accidents


Time:

2026-08-07

Abnormal noises are occurring inside the transformer. These noises may be caused by the following: severe overload causing a heavy "humming" sound; poor internal contact or breakdown points causing a "squeaking" or "crackling" discharge sound; loose parts on the transformer top cover connecting bolts causing the transformer core to vibrate and produce loud noise; a grounding or short-circuit fault in the power grid causing a large current to flow through the windings, producing loud noise; connection of large power equipment or equipment that generates harmonic currents to the transformer causing a "wailing" sound; core resonance causing fluctuating noise; excessively high primary voltage or current; and discharge sounds caused by overvoltage, discharge from windings or leads to the casing, or a broken core grounding wire causing the core to discharge to the casing.

Emergency Measures: When abnormal noises are detected from the transformer, the possible causes should be determined based on the above analysis, and targeted emergency measures should be taken. If abnormal noises emanating from inside the transformer are caused by loose parts or broken winding wires, power should be cut off immediately to prevent further escalation of the accident.

Transformer oil level too high or too low. Normally, changes in oil temperature can alter the oil level. As the oil temperature changes, the oil level will also change within a certain range. However, under abnormal conditions, faults such as oil leakage, water leakage, and other accidents can also cause abnormal changes in the oil level. Furthermore, changes in oil temperature are related to load conditions and ambient temperature. When the oil level change is inconsistent with these factors, it may be a false oil level reading. Causes of false oil level readings include: blocked oil level gauge pipe; blocked vent hole in the explosion-proof pipe. Additionally, an excessively high oil level will cause oil overflow; an excessively low oil level may expose internal leads or even coils, leading to internal discharge.

Handling methods and emergency measures: For transformers with gas relay protection, disconnect the trip circuit to prevent false tripping. On-duty electrical equipment operators should frequently check the oil level gauge indication; if the oil level is too high, drain an appropriate amount of oil; if the oil level is too low, add oil promptly. If the problem is caused by transformer oil leakage, power outage maintenance and other emergency measures should be taken. If abnormal oil spraying is detected from the oil tank or explosion-proof pipe, the transformer power supply should be immediately cut off to prevent the escalation of the fault and accident.

Transformer oil deterioration or sudden temperature increase. During operation, the main functions of transformer oil are cooling and insulation. Prolonged overheating or water ingress into the casing, leading to moisture absorption, will deteriorate the oil quality. This will be observed through the oil level indicator, showing an abnormally darkened or blackened oil color; sample analysis will reveal the presence of carbon particles and moisture, increased acid value, decreased flash point, and reduced insulation strength. This situation can easily lead to breakdown discharge between the windings and the casing, causing serious accidents. A sudden increase in oil temperature during normal transformer operation is often caused by internal overheating. Core fire, inter-turn short circuits in the windings, loose internal screws, cooling device malfunction, and severe transformer overload can all cause a sudden increase in oil temperature.

Solutions and Emergency Measures: If the oil color is found to be abnormally darkened or blackened, the insulating oil needs to be regenerated and filtered. If the oil temperature rises suddenly due to load factors, the load can be appropriately reduced or adjusted. If the oil temperature rises suddenly due to other abnormal conditions, the power should be immediately cut off and the transformer should be thoroughly inspected.

Transformer Fire. When a fault occurs inside the transformer and is not dealt with in time, it may catch fire. When a transformer catches fire, the insulating oil in the tank burns and turns into gas, causing the tank to rupture. The burning insulating oil will spray out of the transformer, causing equipment damage and property loss. Internal or external short circuits in the transformer conductors, severe overload, lightning strikes, or the introduction of external ignition sources into the transformer can all lead to a transformer fire.

Emergency Measures: a. Strengthen the operation and management of the transformer, and try to control the oil temperature inside the transformer to not exceed 85℃; regularly inspect and test the electrical performance of the transformer, and regularly conduct oil deterioration tests. b. Small-capacity transformers should have overcurrent protection such as fuses on both the high and low voltage sides; large-capacity transformers should be equipped with gas protection and differential protection as required. When high-voltage transformers are protected by fuses, for transformers below 100KVA, the rated current of the fuse should be selected at 2-3 times the rated current of the transformer. For transformers above 100KVA, the fuse should be selected at 1.5-2 times the rated current. c. The room where the transformer is installed should be a Class I fire-resistant building; it should have good ventilation, with the highest exhaust temperature not exceeding 45℃, and the temperature difference between the intake and exhaust air controlled within 15℃; the room should have oil-blocking facilities and an oil storage pit; according to safety requirements, no two transformers should be installed in the same room. d. The transformer load should be checked regularly, and the load should not exceed the safety management regulations. e. Transformers connected by overhead conductors should be equipped with surge arresters according to regulations, and the surge protection devices should be inspected before the rainy season. f. A dedicated person should be assigned to maintain the transformer, and there should be a patrol and inspection system and records. Maintain the normal, safe, and economical operation of the transformer and the cleanliness of the working environment.